Products Introduction

Product Brief
The NI cFP-AO-210 is an 8-channel 12-bit voltage analog output module for Compact FieldPoint distributed I/O systems. It provides 0-10 V control signals for actuators and variable devices, widely used as spare replacement for legacy industrial automation systems.

Product Details
The NI cFP-AO-210 is a Compact FieldPoint I/O module designed for installation on cFP backplanes. It features eight single-ended voltage output channels with 12-bit resolution, generating standard 0 to 10 V control signals with overranging up to 10.2 V.
Under standard operation, each channel can source or sink 1 mA. When connected to an optional 15–30 VDC external power supply, the drive capacity increases to 10 mA for heavier loads. The maximum update rate reaches 200 updates per second, and monotonic performance is guaranteed across the full operating temperature range.
It has built-in overvoltage protection from -10 V to 20 V. All channels default to 0 V when powered on for safe startup. LED indicators on the front panel show power status and current limit alarm for each channel, helping technicians quickly identify wiring or load faults.
Communication is carried out through the internal backplane bus with Compact FieldPoint controllers or network interfaces. Output configuration and status monitoring can be completed in LabVIEW, NI MAX and FieldPoint OPC Server.
This is an end-of-life legacy NI module, compatible only with Compact FieldPoint hardware and matching drivers. It is mainly stocked to maintain existing automation nodes. New projects usually select CompactRIO C-series analog output modules instead.
Rugged industrial construction supports DIN rail cabinet mounting. Typical applications include variable drive setpoint adjustment, proportional actuator control and voltage-based closed-loop process control.

Product Parameters
Part Number: cFP-AO-210
Brand: National Instruments (NI)
Channel Count: 8 voltage output channels
Resolution: 12-bit
Output Range: 0–10 V, overranging to 10.2 V
Max Update Rate: 200 updates/s
Standard Drive Current: 1 mA
Drive Current (with external power): 10 mA
External Power Option: 15 VDC to 30 VDC
Protection: Overvoltage protection (-10 V ~ 20 V)
Power-Up State: 0 V for all channels
Mounting: Install on Compact FieldPoint backplane
Compatible Platform: All Compact FieldPoint backplanes and controllers
Supported Software: LabVIEW, NI MAX, FieldPoint OPC Server
Product Status: End of Life (EOL)
Typical Application: 0-10V analog control output, actuator setpoint control, legacy FieldPoint spare replacement

Tags: NI cFP-AO-210 cFP-AO-210 module Compact FieldPoint voltage AO NI 8 channel voltage output