Products Introduction
Product Brief
The NI cFP-1808 779463-01 is an 8-slot Compact FieldPoint Ethernet network backplane with integrated RS232 serial port, designed for distributed industrial measurement and control. It acts as a communication gateway to connect up to eight cFP I/O modules to TCP/IP Ethernet networks, supporting event-driven I/O data transmission, remote monitoring and automation control. It is widely used for factory distributed data acquisition, environmental monitoring and legacy FieldPoint system upgrade and spare replacement.

Product Details
The NI cFP-1808 is a rugged industrial backplane in the Compact FieldPoint product family, featuring eight expansion slots to accommodate cFP series I/O modules, including analog input, analog output, digital I/O, thermocouple, RTD and relay modules. Compared with the 4-slot cFP-1804, this 8-slot model supports more I/O channels within a single backplane unit, suitable for larger distributed field nodes.
It is equipped with an auto-negotiating 10/100 Mbps Ethernet RJ45 port compliant with IEEE802.3 standard, and one RS232 DCE serial port for extra serial device connection. It adopts event-driven communication mode, only uploading data when I/O values change, which effectively reduces Ethernet bandwidth occupation. It supports OPC server and can work seamlessly with LabVIEW, LabWindows/CVI and FieldPoint API.
The unit is built to withstand harsh industrial conditions. It supports DIN rail mounting inside electrical cabinets. It has wide-range DC power input from 11 VDC to 30 VDC, with a maximum output power of 9 W for loaded I/O modules. It provides built-in diagnostic indicators and IP reset dip switches for easy network configuration and on-site troubleshooting.
This is an end-of-life legacy NI hardware. It is mainly supplied as replacement spare parts for existing running Compact FieldPoint systems. It can be combined with cFP real-time controllers to expand remote I/O nodes over Ethernet. Typical usage covers remote temperature and pressure collection, building automation monitoring, test cell distributed signal acquisition and industrial equipment retrofitting projects.

Product Parameters
Part Number: cFP-1808, 779463-01
Brand: National Instruments (NI)
Slot Count: 8 slots for Compact FieldPoint I/O modules
Network Interface: 10/100 Mbps Ethernet, RJ45
Serial Interface: 1 x RS232 DCE port
Communication Protocol: TCP/IP, event-driven I/O transmission, OPC compatible
Power Input: 11 VDC to 30 VDC
Max Power to I/O Modules: 9 W
Mounting Type: DIN rail mount
Operating Temperature: -40 °C to 70 °C
Storage Temperature: -55 °C to 85 °C
Humidity Range: 10% to 90% RH, non-condensing
Isolation Test Voltage: 2300 Vrms (5 seconds)
Weight: 1595 g
Compatible Software: LabVIEW, LabWindows/CVI, FieldPoint OPC Server
Product Status: End of Life (EOL)
Typical Application: Distributed industrial monitoring, remote data acquisition, factory automation, legacy FieldPoint system spare replacement
Tags: NI cFP-1808 779463-01 Compact FieldPoint backplane NI distributed I/O module